Comparison of Different Fin and Tube Compact Heat Exchanger with Longitudinal Vortex Generator in CFU-CFD Configurations

Barquin, Katherine; Valencia, Alvaro

Abstract

Over the last decades several studies have searched for improved Fin and Tube Heat Exchanger (FTHE) designs capable of providing the best thermo-hydraulic performance. The present study aims at quantifying and comparing the thermo-hydraulic performance of different FTHE configurations. Six different designs were analyzed. The first FTHE consisted of an in-line circular tube arrangement and the last one was a FTHE with staggered oval tube with two pairs of Delta Winglet Vortex Generators (DWVG) in common flow up-common flow down (CFU-CFD) configuration. The best performance was obtained using DWVG in CFU-CFD orientation. This configuration enabled a 90% increase of the thermal performance factor when compared with the first case, using only two pairs of vortex generator's per tube.

Más información

Título según WOS: Comparison of Different Fin and Tube Compact Heat Exchanger with Longitudinal Vortex Generator in CFU-CFD Configurations
Título de la Revista: INTERNATIONAL JOURNAL OF HEAT AND TECHNOLOGY
Volumen: 39
Número: 5
Editorial: INT INFORMATION ENGINEERING TECHNOLOGY ASSOC
Fecha de publicación: 2021
Página de inicio: 1523
Página final: 1531
DOI:

10.18280/ijht.390514

Notas: ISI