Harmonic distortion and power factor assessment in city street gas discharge lamps

Rios S.; Castañeda R.; Veas D.

Keywords: models, distribution, transmission, networks, power, outdoor, factor, distortion, discharge, analysis, lighting, sampling, harmonic, mathematical, processes, Electric, Random, lamps

Abstract

The current and voltage harmonic spectrum, and power factor in gas discharge lamps: Sodium (Na)-high pressure and Mercury (Hg) in actual use in public street lighting have been measured. A sample of nearby 360 gas discharge lamps (Na, Hg) of different rated power was obtained by simple random sampling over a universe of approximately 15,000 lamps. An "equivalent" current harmonic spectrum for gas discharge lamps is proposed, which is independent of the type of gas and the lamp rated power. This current spectrum can be used to integrate gas discharge lamp models for harmonic distortion level assessment in distribution networks. The relation of this equivalent current harmonic spectrum with: i) lamp voltage waveform, ii) type of lamp (Na, Hg), and iii) power factor-capacitor lamp, is analyzed. © 1995 IEEE.

Más información

Título de la Revista: IEEE TRANSACTIONS ON POWER DELIVERY
Volumen: 11
Número: 2
Editorial: IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
Fecha de publicación: 1996
Página de inicio: 1013
Página final: 1018
URL: http://www.scopus.com/inward/record.url?eid=2-s2.0-0030126269&partnerID=q2rCbXpz